Call Us Toll-Free: (877) 268-3700 | sales@grossautomation.com
B6 & B7 | MINIATURE CONTACTORS | NON-REVERSING | 3 PHASE
APPLICATION
- Low power consumption coils
- Self-lifting cable clamps
- Panel or DIN rail mounting
- Snap-on accessories
- UL Listed, file # E39231
- Applications include use in machines, electrical appliances, building automation systems, heating systems, overhead door applications, etc.
NON-REVERSING WITH SCREW CONNECTIONS
General Purpose AC1 |
Maximum Motor FLA AC3 |
3 Phase Motor Horsepower | Single Phase | Number of Power Poles |
Auxiliary Contacts |
Catalog Number | ||||
208V | 230V | 460V | 600V | 120V | 230V | |||||
AC OPERATED | ||||||||||
12 | 6.8 | 1 | 2 | 3 | 1 | 1/2 | 1 | 3 3 4 |
1 N.O. 1 N.C. - |
B6-30-10-Δ B6-30-01-Δ B6-40-00-Δ |
16 | 9.6 | 2 | 3 | 5 | 5 | 1 | 2 | 3 3 4 |
1 N.O. 1 N.C. - |
B7-30-10-Δ B7-30-01-Δ B7-40-00-Δ |
DC OPERATED | ||||||||||
12 | 6.8 | 1 | 2 | 3 | 1 | 1/2 | 1 | 3 | 1 N.O. 1 N.C. |
BC6-30-10-Δ BC6-30-01-Δ |
16 | 9.6 | 2 | 3 | 5 | 5 | 1 | 2 | 3 | 1 N.O. 1 N.C. |
BC7-30-10-Δ BC7-30-01-Δ |
NON-REVERSING WITH FLAT PIN CONNECTIONS
General Purpose AC1 |
Maximum Motor FLA AC3 |
3 Phase Motor Horsepower | Single Phase | Number of Power Poles |
Auxiliary Contacts |
Catalog Number | ||||
208V | 230V | 460V | 600V | 120V | 230V | |||||
AC OPERATED | ||||||||||
12 | 6.8 | 1 | 2 | 3 | 1 | 1/2 | 1 | 3 3 4 |
1 N.O. 1 N.C. - |
B6-30-10-FΔ B6-30-01-FΔ B6-40-00-FΔ |
16 | 9.6 | 2 | 3 | 5 | 5 | 1 | 2 | 3 3 4 |
1 N.O. 1 N.C. - |
B7-30-10-FΔ B7-30-01-FΔ B7-40-00-FΔ |
DC OPERATED | ||||||||||
12 | 6.8 | 1 | 2 | 3 | 1 | 1/2 | 1 | 3 | 1 N.O. 1 N.C. |
BC6-30-10-FΔ BC6-30-01-FΔ |
16 | 9.6 | 2 | 3 | 5 | 5 | 1 | 2 | 3 | 1 N.O. 1 N.C. |
BC7-30-10-FΔ BC7-30-01-FΔ |
NON-REVERSING WITH SOLDERING PIN CONNECTIONS
General Purpose AC1 |
Maximum Motor FLA AC3 |
3 Phase Motor Horsepower | Single Phase | Number of Power Poles |
Auxiliary Contacts |
Catalog Number | ||||
208V | 230V | 460V | 600V | 120V | 230V | |||||
AC OPERATED | ||||||||||
12 | 6.8 | 1 | 2 | 3 | 1 | 1/2 | 1 | 3 3 4 |
1 N.O. 1 N.C. - |
B6-30-10-PΔ B6-30-01-PΔ B6-40-00-PΔ |
16 | 9.6 | 2 | 3 | 5 | 5 | 1 | 2 | 3 3 4 |
1 N.O. 1 N.C. - |
B7-30-10-PΔ B7-30-01-PΔ B7-40-00-PΔ |
DC OPERATED | ||||||||||
12 | 6.8 | 1 | 2 | 3 | 1 | 1/2 | 1 | 3 | 1 N.O. 1 N.C. |
BC6-30-10-PΔ BC6-30-01-PΔ |
16 | 9.6 | 2 | 3 | 5 | 5 | 1 | 2 | 3 | 1 N.O. 1 N.C. |
BC7-30-10-PΔ BC7-30-01-PΔ |
∆ Coil voltage suffix. Refer to Coil Voltage Selection Chart and substitute the desired coil voltage suffix for the Δ.
COIL VOLTAGE SELECTION CHART
Volts | ||||||||||
12 | 24 | 42 | 48 | 110/125 | 110/120 | 220 | 220/240 | 380/415 | ||
AC 40-450 Hz | F | L | G | 1 | 2 | M | ||||
DC | U | Y | V | W | P | R |