A9 - AF750 COMBINATION STARTERS | CIRCUIT BREAKER TYPE | REVERSING | 3 PHASE |

DESCRIPTION

  • Maximum UL/CSA horsepower ratings
  • Available with ABB non-fusible or fusible disconnect switches and MCP, thermal Magnetic or electronic trip type circuit breakers.
  • Compact space saving design
  • Double break contact design
  • Lowest possible contact bounce
  • UL Listed
STANDARD PART NUMBERS
UL Motor
Switching Current
Maximum Ratings - UL Listed UL Type 1
(Indoor Metal)
UL Type 3R
(Outdoor Metal)
UL Listed 12
(Metal Dustight)
Maximum Motor Horsepower Ratings      
200/208V 230/240V 460/480V 575/600V Catalog Number Catalog Number Catalog Number
UL RATED
9 2 2 5 7.5 12M1-2Δ‡ 12M3-2Δ‡ 12M2-2Δ‡
11 3 3 7.5 10 22M1-2Δ‡ 22M3-2Δ‡ 22M2-2Δ‡
17 5 5 10 15 32M1-2Δ‡ 32M3-2Δ‡ 32M2-2Δ‡
28 7.5 10 20 25 42M1-2Δ‡ 42M3-2Δ‡ 42M2-2Δ‡
34 10 10 25 30 52M1-2Δ‡ 52M3-2Δ‡ 52M2-2Δ‡
42 10 15 30 40 62M1-2Δ‡ 62M3-2Δ‡ 62M2-2Δ‡
54 15 20 40 50 72M1-2Δ‡ 72M3-2Δ‡ 72M2-2Δ‡
65 20 25 50 50 82M1-2Δ‡ 82M3-2Δ‡ 82M2-2Δ‡
80 25 30 60 75 92M1-2Δ‡ 92M3-2Δ‡ 92M2-2Δ‡
110 30 40 75 100 A2M1-2Δ‡ A2M3-2Δ‡ A2M2-2Δ‡
130 40 50 100 125 B2M1-2Δ‡ B2M3-2Δ‡ B2M2-2Δ‡
156 50 60 125 150 C2M1-2Δ‡ C2M3-2Δ‡ C2M2-2Δ‡
192 60 75 150 200 D2M1-2Δ‡ D2M3-2Δ‡ D2M2-2Δ‡
248 75 100 200 250 E2M1-2Δ‡ E2M3-2Δ‡ E2M2-2Δ‡
302 100 100 250 300 F2M1-2Δ‡ F2M3-2Δ‡ F2M2-2Δ‡
414 125 150 350 400 G2M1-2Δ‡ G2M3-2Δ‡ G2M2-2Δ‡
480 150 200 400 500 H2M1-70Δ‡ H2M3-70Δ‡ H2M2-70Δ‡
590 200 250 500 600 T2M1-70Δ‡ T2M3-70Δ‡ T2M2-70Δ‡
810 250 300 600 700 U2M1-70Δ‡ U2M3-70Δ‡ U2M2-70Δ‡

 

UL Motor
Switching Current
Maximum Ratings - UL Listed UL Type 4
(Watertight)
UL Type 4X
(Stainless Steel)
UL Type 1, 3R, 4, 4X & 12
(Plastic)
Maximum Motor Horsepower Ratings      
200/208V 230/240V 460/480V 575/600V Catalog Number Catalog Number Catalog Number
UL RATED
9 2 2 5 7.5 12M4-2Δ‡ 12MX-2Δ‡ 12MP-2Δ‡
11 3 3 7.5 10 22M4-2Δ‡ 22MX-2Δ‡ 22MP-2Δ‡
17 5 5 10 15 32M4-2Δ‡ 32MX-2Δ‡ 32MP-2Δ‡
28 7.5 10 20 25 42M4-2Δ‡ 42MX-2Δ‡ 42MP-2Δ‡
34 10 10 25 30 52M4-2Δ‡ 52MX-2Δ‡ 52MP-2Δ‡
42 10 15 30 40 62M4-2Δ‡ 62MX-2Δ‡ 62MP-2Δ‡
54 15 20 40 50 72M4-2Δ‡ 72MX-2Δ‡ 72MP-2Δ‡
65 20 25 50 50 82M4-2Δ‡ 82MX-2Δ‡ 82MP-2Δ‡
80 25 30 60 75 92M4-2Δ‡ 92MX-2Δ‡ 92MP-2Δ‡
110 30 40 75 100 A2M4-2Δ‡ A2MX-2Δ‡ A2MP-2Δ‡
130 40 50 100 125 B2M4-2Δ‡ B2MX-2Δ‡ B2MP-2Δ‡
156 50 60 125 150 C2M4-2Δ‡ C2MX-2Δ‡ C2MP-2Δ‡
192 60 75 150 200 D2M4-2Δ‡ D2MX-2Δ‡ D2MP-2Δ‡
248 75 100 200 250 E2M4-2Δ‡ E2MX-2Δ‡ E2MP-2Δ‡
302 100 100 250 300 F2M4-2Δ‡ F2MX-2Δ‡ F2MP-2Δ‡
414 125 150 350 400 G2M4-2Δ‡ G2MX-2Δ‡ -
480 150 200 400 500 H2M4-70Δ‡ H2MX-70Δ‡ -
590 200 250 500 600 T2M4-70Δ‡ T2MX-70Δ‡ -
810 250 300 600 700 U2M4-70Δ‡ U2MX-70Δ‡ -
Overload relay suffix code. Select from Overload Relay Selection Chart. Overload relays are required for all combination starters. If overload relay is provided by customer, substitute an "X" in place of the.
‡‡ MCP or breaker rating. Select appropriate code.
MOTOR CIRCUIT PROTECTOR DATA
                               

Motor
Full Load
Amps

MCP
Continous
Rating
Suffix
Code

Catalog
Number
Starter Size 1.5X 2X 4X 5X 6X 7X 8X 9X 10X 11X 12X
.92–2.76 3 A S3L003MW 0 - - 12 15 18 21 24 27 30 33 36
1.53–4.61 5 B S3L005MW 0 - - 20 25 30 35 40 45 50 55 60
3.07–9.23 10 C S3L010MW 0 - - 40 50 60 70 80 90 100 110 120
7.69–23.08 25 D S3L025MW 1 - - 100 125 150 175 200 225 250 275 300
15.38–46.15 50 E S3L050MW 2 - - 200 250 300 350 400 450 500 550 600
30.77–92.31 100 F S3L100MW 3 - - 400 500 600 700 800 900 1000 1100 1200
46.15–138.46 150 G S3L150MW 4 - - 600 750 900 1050 1200 1350 1500 1650 1800
28.85–230.77 250 H S4L250MW 4 375 500 1000 - 1500 - 2000 - 2500 - 3000
46.15–369.23 400 J S5L400MW 5 600 800 1600 - 2400 - 3200 - 4000 - 4800
69.23–553.85 600 K S6L600MW 6 900 1200 2400 - 3600 - 4800 - 6000 - 7200
92.31–738.46 800 L S6L800MW 7 1200 1600 3200 - 4800 - 6400 - 8000 - 9600
115.38–923.07 1000 M S7H1000MW 7 1500 2000 4000 - 6000 - 8000 - 10,000 - 12,000
138.46–1107.69 1200 N S7H1200MW 7 1800 2400 4800 - 7200 - 9600 - 12,000 - 14,400
COIL VOLTAGE SELECTION CHART (A9-A300)
Hz Cntr Type Volts
    24 110 120 208 220 240 440 480 500 600
60 A 1   2 3   4 5 6   7
50 A 1 2     4       7  
COIL VOLTAGE SELECTION CHART (400-A750)
Hz Type 100 - 250 250 - 500
50/60 AF 70 71
CONTROL TRANSFORMER VOLTAGE SELECTION CHART
  Volts
Hz Type 200 - 208/120 240/120 460 - 480/120 575 - 600/120
50/60 A/AF A B C D
200 - 208/24 240/24 460 - 480/24 575 - 600/24
E F G H
CONTROL TRANSFORMER OPTION
   
Contactor Size VA Rating
A9 - A40 50
A50 - A75 75
A95 - A110 100
A145 - A185 150
A210 - A300 250
A400 - A460 150
A580 - A750 250
MAXIMUM SHORT CIRCUIT RATINGS FOR UL LISTED COMBINATION STARTERS
         
Contactor Size Maximum
MCP
480VAC
KA at
480VAC
MCP
600VAC
KA at
600VAC
A9 S3L050MW 35 S3L010MW 35
A12 S3L050MW 35 S3L010MW 35
A16 S3L050MW 35 - -
A26 S3L100MW 35 S3L100MW 35
A30 S3L150MW 65 - -
A40 S3L150MW 65 - -
A50 S3L150MW 85 S3L150MW 35
A63 S4L250MW 85 - -
A75 S4L250MW 85 - -
A95 S4L250MW 85 S4L250MW 35
A110 S4L250MW 85 S4L250MW 35
A145 S5L400MW 85 S4L250MW 10
A185 S5L400MW 85 S4L250MW 10
A210 S6L800MW 85 S4L250MW 18
A260 S6L800MW 85 S5L400MW 18
A300 S6L800MW 85 S5L400MW 18
A400 S7H1200MW 85 Please Call Please Call
A460 S7H1200MW 85 Please Call Please Call
A580 S7H1200MW 85 Please Call Please Call
A750 S7H1200MW 85 Please Call Please Call