Call Us Toll-Free: (877) 268-3700 | Mon-Fri: 8AM-5PM CST
Call Us Toll-Free: (877) 268-3700 | sales@grossautomation.com
STARTER SELECTION BY MOTOR HORSEPOWER & VOLTAGE

DESCRIPTION

  • Maximum UL/CSA horsepower ratings
  • Compact space-saving design
  • Double break contact design

COIL SELECTION

All AC operated catalog numbers include a 120VAC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number.
MAXIMUM UL/CSA RATINGS - 3 PHASE
Motor Horsepower Complete Starter Starter Components
3 Phase, 1800 RPM1   Contactor Overload Relay
200V 230V 460V 575V Catalog Number Catalog Number Catalog Number
 
- - - 1/4 11-2C A9-30-10-84 TA25DU0.4 (0.25 – .4)
- - 1/4, 1/3 1/3 11-2D A9-30-10-84 TA25DU0.63 (0.4 – .63)
- - - 1/2 11-2E A9-30-10-84 TA25DU1.0 (0.63 – 1.0)
- - 1/2 3/4 11-2F A9-30-10-84 TA25DU1.4 (1.0 – 1.4)
- - 3/4 - 11-2G A9-30-10-84 TA25DU1.8 (1.3 – 1.8)
- 1/2 1 1.5 11-2H A9-30-10-84 TA25DU2.4 (1.7 – 2.4)
1/2 - 1.5 2 11-2J A9-30-10-84 TA25DU3.1 (2.2 – 3.1)
3/4 3/4 2 - 11-2K A9-30-10-84 TA25DU4.0 (2.8 – 4.0)
- 1 - 3 11-2L A9-30-10-84 TA25DU5.0 (3.5 – 5.0)
1 1.5 3 5 11-2M A9-30-10-84 TA25DU6.5 (4.5 – 6.5)
2 2 5 - 11-2N A9-30-10-84 TA25DU8.5 (6.0 – 8.5)
- - - 7.5 11-2P A9-30-10-84 TA25DU11 (7.5 – 11)
3 3 7.5 10 21-2Q A12-30-10-84 TA25DU14 (10 – 14)
5 5 10 15 31-2R A16-30-10-84 TA25DU19 (13 – 19)
- 7.5 15 20 41-2S A26-30-10-84 TA25DU25 (18 – 25)
7.5 10 20 25 41-2T A26-30-10-84 TA25DU32 (24 – 32)
10 10 - - 51-2B A30-30-10-84 TA42DU32 (22 – 32)
- - 25 30 51-2C A30-30-10-84 TA42DU42 (29 – 42)
10 15 30 40 61-2C A40-30-10-84 TA42DU42 (29 – 42)
15 - 40 50 71-2D A50-30-11-84 TA75DU52 (36 – 52)
- 20 - - 71-2E A50-30-11-84 TA75DU63 (45 – 63)
20 - - - 81-2F A63-30-11-84 TA75DU80 (60 – 80)
- - 50 60 81-2F A63-30-11-84 TA75DU80 (60 – 80)
25 30 60 75 91-2F A75-30-11-84 TA75DU80 (60 – 80)
- 40 75 100 A1-2B A110-30-11-84 TA110DU110 (80 – 110)
40 - - - B1-2C A145-30-11-84 TA200DU135 (100 – 135)
- 50 100 125 B1-2D A145-30-11-84 TA200DU150 (110 – 150)
50 60 125 150 C1-2E A185-30-11-84 TA200DU175 (130 – 175)
60 75 150 200 D1-2E3 A210-30-11-84 E320D4320 (105-320)
75 100 200 250 E1-2E3 A260-30-11-84 E320D4320 (105-320)
100 - 250 300 F1-2E3 A300-30-11-84 E320D4320 (105-320)
125 125, 150 350 400 G1-70E5 AF400-30-11-70 E500DU500 (170 – 500)
150 200 400 500 H1-70E5 AF460-30-11-70 E500DU500 (170 – 500)
200 250 500 600 T1-70E8 AF580-30-11-70 E800DU800 (270 – 800)
250 300 600 700 U1-70E8 AF750-30-11-70 E800DU800 (270 – 800)
CAUTION: The above ratings are based on average motor FLA. Actual FLA on the motor nameplate should be used for overload relay setting.
COIL VOLTAGE SELECTION CHART (A9-A300)
Hz Cntr Type Volts
    24 110 120 208 220 240 440 480 500 600
60 A 1   2 3   4 5 6   7
50 A 1 2     4       7  
COIL VOLTAGE SELECTION CHART (400-A750)1
Hz Type 100 - 250 250 - 500
50/60 AF 70 71
NEMA SIZES & RATINGS - 3 PHASE
  Motor Horsepower Complete Starter Starter Components
  3 Phase, 1800 RPM1   Contactor Overload Relay
NEMA Size 200V 230V 460V 575V Catalog Number Catalog Number Catalog Number
   
00 - - - 1/4 J1-2C A9N00-30-10-84 TA25DU0.4 (0.25 – .4)
- - - 1/3 J1-2D A9N00-30-10-84 TA25DU0.63 (0.4 – .63)
- - 1/4 1/2 J1-2E A9N00-30-10-84 TA25DU1.0 (0.63 – 1.0)
- 1/4 1/3, 1/2 - J1-2F A9N00-30-10-84 TA25DU1.4 (1.0 – 1.4)
- 1/3 3/4 3/4 J1-2G A9N00-30-10-84 TA25DU1.6 (1.3 – 1.6)
1/3, 1/4 1/2 1 1 J1-2H A9N00-30-10-84 TA25DU2.4 (1.7 – 2.4)
1/2 - - 1.5, 2 J1-2J A9N00-30-10-84 TA25DU3.1 (2.2 – 3.1)
3/4 3/4 1.5, 2 - J1-2K A9N00-30-10-84 TA25DU4.0 (2.8 – 4.0)
- 1 - - J1-2L A9N00-30-10-84 TA25DU5.0 (3.5 – 5.0)
1 1.5 - - J1-2M A9N00-30-10-84 TA25DU6.5 (4.5 – 6.5)
1.5 - - - J1-2N A9N00-30-10-84 TA25DU8.5 (6.0 – 8.5)
0 - - - 3 K1-2L A16N0-30-10-84 TA25DU5.0 (3.5 – 5.0)
- - 3 5 K1-2M A16N0-30-10-84 TA25DU6.5 (4.5 – 6.5)
2 2 5 - K1-2N A16N0-30-10-84 TA25DU8.5 (6.0 – 8.5)
3 3 - - K1-2P A16N0-30-10-84 TA25DU11 (7.5 – 11)
1 - - - 7.5 L1-2P A26N1-30-10-84 TA25DU11 (7.5 – 11)
- - 7.5 10 L1-2Q A26N1-30-10-84 TA25DU14 (10 – 14)
5 5 10 - L1-2R A26N1-30-10-84 TA25DU19 (13 – 19)1
7.5 7.5 - - L1-2S A26N1-30-10-84 TA25DU25 (18 – 25)
2 - - - 15 M1-2R A50N2-30-11-84 TA25DU19 (13 – 19)
- - 15 20 M1-2A A50N2-30-11-84 TA75DU25 (18 – 25)
- 10 20 25 M1-2B A50N2-30-11-84 TA75DU32 (22 – 32)
10 15 25 - M1-2C A50N2-30-11-84 TA75DU42 (29 – 42)
3 - - - 30 N1-2C A75N3-30-11-84 TA75DU42 (29 – 42)
15 - 30 40 N1-2D A75N3-30-11-84 TA75DU52 (36 – 52)
20 20 40 50 N1-2E A75N3-30-11-84 TA75DU63 (45 – 63)
25 25, 30 50 - N1-2F A75N3-30-11-84 TA75DU80 (60 – 80)
4 - - 60 60, 75 P1-2A A145N4-30-11-84 TA200DU90 (65 – 90)
30 40 75 100 P1-2B A145N4-30-11-84 TA200DU110 (80 – 110)
40 50 100 - P1-2C A145N4-30-11-84 TA200DU135 (100 – 135 )
5 50, 60, 75 60, 75, 100 125, 150, 200 200 Q1-2E3 A260N5-30-11-84 E320DU320 (105-320)
- 100 200 - A260N5-30-11-84 E320DU320 (105-320)
6 100, 125 125, 150 250, 300 250, 300 R1-70E5 AF460N6-3011-70 E500DU500 (170 - 500)
150 200 400 400 AF460N6-3011-70 E500DU500 (170 - 500)
7 - 250, 300 500, 600 500, 600 S1-70E8 AF750N7-3011-70 E800DU800 (270 - 800)
CAUTION: The above ratings are based on average motor FLA. Actual FLA on the motor nameplate should be used for overload relay setting.
COIL VOLTAGE SELECTION CHART (A9-A300)
Hz Cntr Type Volts
    24 110 120 208 220 240 440 480 500 600
60 A 1   2 3   4 5 6   7
50 A 1 2     4       7  
COIL VOLTAGE SELECTION CHART (400-A750)1
Hz Type 100 - 250 250 - 500
50/60 AF 70 71
CONTROL TRANSFORMER VOLTAGE SELECTION CHART
  Volts
Hz Type 200 - 208/120 240/120 460 - 480/120 575 - 600/120
50/60 A/AF A B C D
200 - 208/24 240/24 460 - 480/24 575 - 600/24
E F G H
1 AF400 - AF750 only.